Services, Analog input point (class id 0ah), Class attributes – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 146: Instances, Class attributes instances, Analog input point (class id 0a

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

136 DeviceNet Objects

Services

Analog Input Point
(Class ID 0A

H

)

The Analog Input Point Object models simple analog measurements
performed by the XM-122 module.

Class Attributes

Instances

Table C.24 Discrete Input Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Class/Instance

Get_Attribute_Single

Returns the contents of the
specified attribute.

10

h

Instance

Set_Attribute_Single

Sets the contents of the
specified attribute.

32

h

Instance

Open

Opens the virtual Setpoint
Multiplier switch.

33

h

Instance

Close

Closes the virtual Setpoint
Multiplier switch.

Table C.25 Analog Input Point Object Class Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

1

Get

Revision

UINT

Revision of the
implemented object.

2

Table C.26 Analog Input Point Object Instances

Instance

Name

Description

1

Gap Measurement 1

Gap measurement for Channel 1

2

Gap Measurement 2

Gap measurement for Channel 2

3

Not 1X Measurement 1

Not 1X measurement for Channel 1

4

Not 1X Measurement 2

Not 1X measurement for Channel 2

5

gSE Overall Measurement 1 gSE Overall measurement for Channel 1

Advertising