Installing the XM-122 gSE Vibration Module 23
Figures 2.9 and 2.10 illustrate the behavior of the NC and NO terminals when
the relay is wired for failsafe, alarm or nonalarm condition or non-failsafe,
alarm or nonalarm condition.
Figure 2.9 Relay Connection - Failsafe, Nonalarm Condition
Non-failsafe, Alarm Condition
Table 2.1 Relay Connections for XM-122
Configured for
Failsafe Operation
Relay 1 Terminals
Nonalarm
Alarm
Wire Contacts
Contact 1
Contact 2
Closed Opened
COM
47
50
NO
48
49
Opened
Closed
COM 47
50
NC
46
51
Configured for
Non-failsafe Operation
Relay 1 Terminals
Nonalarm
Alarm
Wire Contacts
Contact 1
Contact 2
Closed
Opened
COM
47
50
NC
46
51
Opened
Closed
COM
47
50
NO
48
49