Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 33

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

Installing the XM-122 gSE Vibration Module 23

Figures 2.9 and 2.10 illustrate the behavior of the NC and NO terminals when
the relay is wired for failsafe, alarm or nonalarm condition or non-failsafe,
alarm or nonalarm condition.

Figure 2.9 Relay Connection - Failsafe, Nonalarm Condition

Non-failsafe, Alarm Condition

Table 2.1 Relay Connections for XM-122

Configured for

Failsafe Operation

Relay 1 Terminals

Nonalarm

Alarm

Wire Contacts

Contact 1

Contact 2

Closed Opened

COM

47

50

NO

48

49

Opened

Closed

COM 47

50

NC

46

51

Configured for

Non-failsafe Operation

Relay 1 Terminals

Nonalarm

Alarm

Wire Contacts

Contact 1

Contact 2

Closed

Opened

COM

47

50

NC

46

51

Opened

Closed

COM

47

50

NO

48

49