Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 172

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

162 DeviceNet Objects

7

Get/Set

Delay

USINT

The time period that the
voting logic must be true
before the relay is
activated.

0 to 25.5 seconds
(specified in tenths of seconds)

8

Get/Set

Name

STRING2

A name to help identify
the relay.

18 characters maximum

9

Get/Set

Alarm Level

BYTE

Specifies what alarm
status values will cause
the relay to activate.

0 = Normal
1 = Alert
2 = Danger
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault

10

Get/Set

Alarm Identifier
A

EPATH

Identifies the first alarm
status the relay monitors.

See Parameter Object instances
26 to 30.

11

Get/Set

Alarm Identifier
B

EPATH

Identifies the second
alarm status the relay
monitors.

See Parameter Object instances
31 to 35.

12

Get/Set

Logic

USINT

Indicates the number of
associated alarms that
must have a status value
specified by Alarm Level
in order to activate the
relay.

0 = Ignore Alarm Identifier B
and activate the relay based on
the status of Alarm Identifier
A
.
1 = Activate the relay if the
status of either Alarm
Identifier A
or B matches any
of the statuses specified by
Alarm Level.
2 = Activate the relay if the
status of both Alarm Identifier
A
and B match any of the
statuses specified by Alarm
Level
.

14

Get

Relay Installed

BOOL

Indicates whether an
actual relay is associated
with this instance.

0 = Not installed
1 = Installed

Table C.50 Relay Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics