Instance attributes – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 174

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

164 DeviceNet Objects

Instance Attributes

Table C.52 Spectrum Waveform Measurement Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

Status

BOOL

Indicates if a fault or
alarm has occurred.

0 = Operating without alarms or
faults.
1 = Alarm or fault condition
exists. The Spectrum and
Waveform data may not
represent the actual field value.

4

Get

Data Units

ENGUNIT

The units context of the
Data attributes.

This setting is determined by the
Channel Object’s Output Data
Units
attribute (see page 153.

5

Get

Domain

USINT

The domain used for the
spectrum and waveform
measurements.

0 = Frequency/Time
1 = Order/Position

6

Get/Set

FMAX

REAL

The maximum frequency
or order of the spectrum
data.

0-20000 Hz if Domain = 0.
There are several predetermined
FMAX settings for which
spectrum data can be produced.
If you select an unsupported
value, then the next greater
supported FMAX value will be
used for the spectrum data.

4-40 Orders if Domain = 1.The
Number of Lines value must
be evenly divisible by the FMAX
value or an Invalid Device
Configuration error will be
returned during the Device
Mode Object Start and Save
services.

7

Get/Set

Number of
Spectrum Lines

UDINT

Number of lines or bins in
the spectrum data.

100, 200, 400, or 800

8

Get/Set

Window Type

USINT

The window function to
be applied to the
waveform data prior to
computing the spectrum.

0 = Rectangular
1 = Hamming
2 = Hanning
3 = Flat Top
4 = Kaiser Bessel

9

Get/Set

Period

REAL

The period of the
waveform.

Seconds if Domain = 0.
Cycles if Domain = 1.

10

Get

Number of
Waveform
Points

UDINT

Number of points in the
waveform data.

256, 512, 1024, or 2048

11

Get

Overlap

USINT

The percent overlap
applied to the waveform
data sets used for
calculating the spectrum.

Only 0% supported.