Publication GMSI10-UM013D-EN-P - May 2010

Configuration Parameters 75

Condition

Controls when the alarm should trigger.

Greater than - Triggers the alarm when the
measurement value is greater than or equal to the
Alert and Danger Threshold values.
The Danger Threshold value must be greater than
or equal to the Alert Threshold value for the trigger
to occur.

Less than - Triggers the alarm when the
measurement value is less than or equal to the
Alert and Danger Threshold values.
The Danger Threshold value must be less than or
equal to the Alert Threshold value for the trigger to
occur.

Inside range - Triggers the alarm when the
measurement value is equal to or inside the range
of the Alert and Danger Threshold values.
The Danger Threshold (High) value must be less
than or equal to the Alert Threshold (High) value
AND the Danger Threshold (Low) value must be
greater than or equal to the Alert Threshold (Low)
value for the trigger to occur.

Outside range - Triggers the alarm when the
measurement value is equal to or outside the
range of the Alert and Danger Threshold values.

The Danger Threshold (High) value must be greater
than or equal to the Alert Threshold (High) value,
AND the Danger Threshold (Low) value must be
less than or equal to the Alert Threshold (Low)
value for the trigger to occur.

Options: Greater Than

Less Than
Inside Range
Outside Range

Note: This parameter is not applicable
for a vector (phase) alarm type or
phase measurement.

Alarm Parameters

Parameter Name

Description

Values/Comments