Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 47

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

Installing the XM-122 gSE Vibration Module 37

Figure 2.26 DC Voltage Signal to Channel 2 Wiring

Connecting an IEPE Accelerometer and Non-Contact Sensor

Figure 2.27 shows the wiring of an IEPE accelerometer to channel 1 and the
wiring of a non-contact sensor to channel 2.

TYPICAL WIRING FOR PROCESS DC VOLTAGE SIGNAL

TO XM-122 VIBRATION MODULE CHANNEL 2

Cable shield not
connected at this end

Shield

1

17

Channel 2 Input Signal

Signal Common

38

Process DC
Source

ATTENTION

Figure 2.27 shows the wiring to the XM-122 module
revision D01 (and later). Earlier revisions of the module do
not
support this wiring configuration. Refer to Appendix
D for information about wiring earlier revisions.

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the terminal base
and not at the transducer. Any convenient Chassis terminal
may be used (see Terminal Block Assignments on page 18).

IMPORTANT

Make certain the IEPE Power parameter for channel 1 is
enabled so power is provided to the accelerometer. Refer
to Channel Transducer Parameters on page 58.