Publication GMSI10-UM013D-EN-P - May 2010

40 Installing the XM-122 gSE Vibration Module

Figure 2.28 Two IEPE Accelerometers and a Non-Contact Sensor Wiring

Connecting a Velocity Sensor and Two Non-Contact Sensors

Figure 2.29 shows the wiring of a velocity sensor and two non-contact sensors
to the terminal base unit. The velocity sensor is wired to channel 1. The first
non-contact sensor is wired to channel 2, and the other non-contact sensor is
wired to the tachometer input signal.

TYPICAL WIRING FOR TWO IEPE ACCELEROMETERS AND

NON-CONTACT SENSOR TO XM-122 VIBRATION MODULE

Shield

Pin A - Signal
Pin B - Common

Cable shield not
connected at this end

0

16

22

6

21

Channel 1 Input Signal

Signal Common

5

37

SIG

-24

COM

17

1

Signal Common

Channel 2 Input Signal

-24V DC

Pin A - Signal
Pin B - Common

Cable shield not
connected at this end

Shield

36

20

4

Tach Input Signal

Signal Common

31

Shield

Shield
Floating

Isolated Sensor Driver

*

*

* Note: Jumpering terminal 5 to terminal 6
configures CH 1 buffer (-5V to +24V)

Jumpering terminal 22 to terminal 6
configures CH 2 buffer (-5V to +24V)

18

IMPORTANT

Figure 2.29 shows the wiring to the XM-122 module
revision D01 (and later). If you have any earlier revision of
the module, refer to Appendix D for wiring information.

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the terminal base
and not at the transducer. Any convenient Chassis terminal
may be used (see Terminal Block Assignments on page 18).