Figures 2.23 and 2.24 sho – Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual
Page 45
Advertising
Publication GMSI10-UM013D-EN-P - May 2010
Installing the XM-122 gSE Vibration Module 35
Figure 2.23 Powered Sensor to Channel 1 Wiring
Figure 2.24 Powered Sensor to Channel 2 Wiring
0
16
37
+24V DC
Common
Signal
5
6
Channel 1 Input Signal
Signal Common
Shield
+24V DC
TYPICAL WIRING FOR MODEL 580 VIBRATION PICKUP
TO XM-122 VIBRATION MODULE CHANNEL 1
Cable shield not
connected at this end
25
Jumpering terminal 5
to terminal 6 configures
CH 1 buffer for -5V to +24V
1
17
38
+24V DC
Common
Signal
6
22
Channel 2 Input Signal
Signal Common
Shield
+24V DC
TYPICAL WIRING FOR MODEL 580 VIBRATION PICKUP
TO XM-122 VIBRATION MODULE CHANNEL 2
Cable shield not
connected at this end
Jumpering terminal 6
to terminal 22 configures
CH 2 buffer for -5V to +24V
25