Rockwell Automation 1440-VSE02-01RA XM-122 gSE Vibration Module User Manual

Page 83

Advertising
background image

Publication GMSI10-UM013D-EN-P - May 2010

Configuration Parameters 73

Fault Time-Out

The number of seconds the module should wait after
the last valid tach pulse before it indicates a
tachometer fault.

Enter a value from 1 to 64 seconds.

Sets the trigger mode. In Auto Trigger mode, the
minimum signal amplitude for triggering is 2 volts
peak-to-peak and minimum frequency is 6 CPM (0.1
Hz).

In Manual Trigger mode, the value entered in
Trigger Threshold is used as the trigger point.
Minimum signal amplitude for triggering is 500
millivolts peak-to-peak and minimum frequency is 1
CPM.

Trigger Hysteresis

The amount of hysteresis around the trigger
threshold. In Auto Trigger mode, the value entered is
a percentage of the peak-to-peak input signal. This
value can range from 0 to 50%.

In Manual Trigger mode, the value entered is a
voltage level. The hysteresis voltage is added to or
subtracted from the threshold voltage to determine
the hysteresis range. The minimum value is 0.12
volts.

% in Auto Trigger mode
Volt in Manual Trigger mode

Trigger Threshold

The signal level to be used as the trigger value when
in Manual Trigger mode.

Enter a value from +16 to -16 volts dc.

Note: This value is not used in Auto
Trigger mode.

Trigger Slope

The input signal slope to be used as the trigger value
when in Manual Trigger mode.

Options: Positive

Negative

Note: This value is not used in Auto
Trigger mode.

Tachometer Signal Processing Parameters

Parameter Name

Description

Values/Comments

XM Configuration
Utility

EDS File

Auto Trigger

Trigger
Mode

XM Configuration
Utility

EDS File

Check = Auto Mode

Auto

Clear = Manual
Mode

Manual