2. Remove the chassis cover, the front panel bezel, and the processor air duct. For

instructions, see see

Section 3.2.1

,

Section 3.2.3

, and

Section 3.2.5

.

3. Remove the drive bay assembly. For instructions, see

Section 5.4.1, “Removing the

Drive Bay Assembly” on page 111

.

4. Remove the power supply module(s). For instructions, see

Section 3.3.2,

“Replacing a Power Supply” on page 31

.

5. Remove the PCI riser card assembly. For instructions, see

Section 4.2.2, “Removing

the PCI Riser Card Assembly” on page 53

.

6. Remove the PCI fan assembly. For instructions, see

Section 5.2.3, “Removing the

PCI Fan Assembly” on page 102

.

7. Remove the CPU fan assembly. For instructions, see

Section 5.2.1, “Removing the

CPU Fans” on page 100

.

8. Disconnect the cable harnesses at the other ends on the T5000PAL server board

and the SFP board.

9. Press down on the metal clip at the base of the PDB assembly to free the PDB

assembly. (

Figure 101

, “A”)

10. Gently pull the PDB assembly off of the placement pegs. (“B”).
11. Lift the PDB from the chassis (“C”).

5.5.2

Installing the Power Distribution Board Back into the Chassis

1. Lower the replacement power distribution board (PDB) into place. (

Figure 102

, “A”)

2. Make sure that the PDB is placed over the placement pegs and gently push down.

(“B”)