Blocks required – Pilz PSS SB HYD, Basic license User Manual

Page 101

Advertising
background image

Modular Block System: Hydraulic Presses

6-39

- Bit 12:

Gate closed, S1 was not open
Remedy: Open gate, check switch, cable and input card and
then carry out function test and reset (input parameter

RSET)

- Bit 13:

Gate closed, S2 was not open
Remedy: Open gate, check switch, cable and input card, carry
out a function test and then reset (input parameter

RSET)

- Bit 14:

RSET input constantly high or set too early
Remedy: If

RSET input was not set too early and is constantly

high: Check switch, cable and input card, then reset (input
parameter

RSET).

If

RSET input was set too early: reset again

(input parameter

RSET)

- Bit 15:

Gate closed,

RSET signal is missing

Remedy: Check all conditions and then reset
(input parameter

RSET)

• Error messages on the CPU-display

- E003

Administration data block has not been initialised
Remedy: Call SB071 in OB120

Global parameters used in the administration data blocks

The global parameter may be set in OB120 using SB071.
• DW1022: Minimum scan time

Blocks required

• DB015, DB016, DB017: Administration data blocks

The data blocks must consist of their total length of 1024 data
words and have READ/WRITE access (see Chapter 5, section
entitled “Administration data blocks...”).

• SB071:

Initialisation of global parameters in DB015, DB016 and DB017