Blocks required – Pilz PSS SB HYD, Basic license User Manual
Page 101
Modular Block System: Hydraulic Presses
6-39
- Bit 12:
Gate closed, S1 was not open
Remedy: Open gate, check switch, cable and input card and
then carry out function test and reset (input parameter
RSET)
- Bit 13:
Gate closed, S2 was not open
Remedy: Open gate, check switch, cable and input card, carry
out a function test and then reset (input parameter
RSET)
- Bit 14:
RSET input constantly high or set too early
Remedy: If
RSET input was not set too early and is constantly
high: Check switch, cable and input card, then reset (input
parameter
RSET).
If
RSET input was set too early: reset again
(input parameter
RSET)
- Bit 15:
Gate closed,
RSET signal is missing
Remedy: Check all conditions and then reset
(input parameter
RSET)
• Error messages on the CPU-display
- E003
Administration data block has not been initialised
Remedy: Call SB071 in OB120
Global parameters used in the administration data blocks
The global parameter may be set in OB120 using SB071.
• DW1022: Minimum scan time
Blocks required
• DB015, DB016, DB017: Administration data blocks
The data blocks must consist of their total length of 1024 data
words and have READ/WRITE access (see Chapter 5, section
entitled “Administration data blocks...”).
• SB071:
Initialisation of global parameters in DB015, DB016 and DB017