Error messages – Pilz PSS SB HYD, Basic license User Manual

Page 105

Advertising
background image

Modular Block System: Hydraulic Presses

6-43

The acknowledgements

FbL1 and FbL2 are also monitored in the static

condition. If there are discrepancies between the set and true condition, an
error message will be issued (

ENBL = 0) and the contactors will be

switched off immediately (

K1 = 0 and K2 = 0). The error will need to be

reset.

It is possible to reset errors via the input parameter

RSET both when ON =

0 and when

ON = 1. However, a prerequisite for setting the enable and,

when

ON = 1, switching on the contactors, is that the signals from the

feedback loops are correct.

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of the administration data block (1st data block), until the

fault has been fully dealt with.

• Error messages in the administration data block

- Bit 00:

Fault as the signal changes at input parameter

ON,

feedback loop 1 (

FbL1) remains open

Remedy: Check contactor, contacts, cable, input card, output
card, value of input parameter

TFbL and all conditions and

then reset (input parameter

RSET)

- Bit 01:

Fault as the signal changes at input parameter

ON,

feedback loop 1 (

FbL1) remains closed

Remedy: Check contactor, contacts, cable, input card, output
card, value of input parameter

TFbL and all conditions and

then reset (input parameter

RSET)

- Bit 02:

Fault as the signal changes at input parameter

ON,

feedback loop 2 (

FbL2) remains open

Remedy: Check contactor, contacts, cable, input card, output
card, value of input parameter

TFbL and all conditions and

then reset (input parameter

RSET)