Modular Block System: Hydraulic Presses

Standard Function Blocks

- Bit 09:

Button pressed without start enable
Remedy: Check enable input, cable, input card and all
conditions, then reset (input parameter

RSET)

- Bit 10:

Synchronisation time error, T1 missing (no “Auf” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter

RSET)

- Bit 11:

Synchronisation time error, T2 missing (no “Auf” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter

RSET)

- Bit 12:

Two-hand control RESET via

MEin (button released)

Remedy: Check switch, cable, input card and all conditions,
then reset (input parameter

RSET)

- Bit 14:

T1 not released (no “Jog” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter

RSET)

- Bit 15:

T2 not released (no “Jog” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter

RSET)

• Error messages on the CPU-display

- None

Global parameters used in administration data block DB015

Global parameters may be set in OB120 using SB070.

• DW1022: Minimum scan time

Blocks required

• DB015:

Administration data block

DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.

SB059