Blocks required, Standard function blocks, Sb059 – Pilz PSS SB HYD, Basic license User Manual
Page 84
6-22
Modular Block System: Hydraulic Presses
Standard Function Blocks
- Bit 09:
Button pressed without start enable
Remedy: Check enable input, cable, input card and all
conditions, then reset (input parameter
RSET)
- Bit 10:
Synchronisation time error, T1 missing (no “Auf” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter
RSET)
- Bit 11:
Synchronisation time error, T2 missing (no “Auf” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter
RSET)
- Bit 12:
Two-hand control RESET via
MEin (button released)
Remedy: Check switch, cable, input card and all conditions,
then reset (input parameter
RSET)
- Bit 14:
T1 not released (no “Jog” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter
RSET)
- Bit 15:
T2 not released (no “Jog” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter
RSET)
• Error messages on the CPU-display
- None
Global parameters used in administration data block DB015
Global parameters may be set in OB120 using SB070.
• DW1022: Minimum scan time
Blocks required
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
SB059