Modular Block System: Hydraulic Presses

6-17

T1.2:

N/C button 1

T1.4:

N/O button 1

T2.2:

N/C button 2

T2.4:

N/O button 2

KU_S:

Contact switchover time between N/O and N/C contact on
pushbuttons
Permitted time range: 1 ... 1000 ms
Format: Constant fixed point number KF00001 … KF01000
Suggested value: KF00100

INFORMATION
If your plant does not run stably using the suggested value, you can
work out the value that suits your plant as follows:
- Select the suggested value as a starting point.
- Increase this value by appropriate time intervals until your plant runs
stably.
Please note:
Entering an excessively high time value for monitoring will reduce the
level of safety on your plant.

RSET:

Reset input
RSET = 0/1-signal edge: Trigger reset

WARNING!
The input parameter

Tipp is not intended for use on presses and therefore

must not be activated on presses.
On presses, this input should be assigned RLO-0 (M110.00).

Tipp:

Mode: “Jog mode using one button and setup speed”
Tipp = 0:

Mode: “Jog mode using one button” is blocked.
To disable jog mode using one button, the input
should be assigned RLO-0 (M110.00).