Output parameters, Standard function blocks, Sb089 – Pilz PSS SB HYD, Basic license User Manual

Page 212

Advertising
background image

6-150

Modular Block System: Hydraulic Presses

Standard Function Blocks

VTyp:

Type of valve to be monitored
VTyp = 0:

Monitoring a directional control valve

VTyp = 1:

Monitoring a poppet valve

(see also under “Function”)

RSET:

Error Reset
RSET = 0/1 pulse edge: Reset fault

It will only be possible to reset an existing fault if
the valve is in its start position (valve de-energised
and acknowledgement from valve is present) and
no start signal is present (

Y1On = 0, Y2On = 0).

Output parameters

ENBL:

Enable flag bit
ENBL = 0: Enable locked

When the valve is switched off (input parameter
Y1On / Y2On = 1/0 pulse edge), the enable is
locked until the valve returns to its start position
(input parameter

S1 = 1 / S2 = 1). This is not an

error. The block will cancel the enable
immediately if it detects a fault.

ENBL = 1: Enable

The block will set the enable if no fault has been
found and the valves are either in operation or in
their start position.

Y1:

Output parameters for operating valve Y1
Y1 = 0:

Valve Y1 off

Y1 = 1:

Valve Y1 on

Y2:

Output parameters for operating valve Y2
Y2 = 0:

Valve Y2 off

Y2 = 1:

Valve Y2 on

ERR:

The output parameter is set as soon as a fault is detected.
ERR = 0:

No fault detected

ERR = 1:

Fault detected

SB089