Block header, Input parameters, Standard function blocks sb069 – Pilz PSS SB HYD, Basic license User Manual

Page 134

Advertising
background image

6-72

Modular Block System: Hydraulic Presses

Standard Function Blocks

SB069

SB069: Monitoring ESPE/AOPDs with guarding function

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 600
Format: Byte constants KF000001 ... KF000600
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).
Value of DW (SSNR) = 0: No error found

GRP

Status flag of the I/O-Group (SafetyBUS p) whose I/O signals
are used for this function (M116.00 for I/O-Group 0 to M116.31
for I/O-Group 31). If the SB is being used without SafetyBUS
p, the input parameter must be assigned RLO-1.

NO_1:

Output signal 1 from the ESPE/AOPD (normally open 1)
NO_1 = 0: Protected field broken
NO_1 = 1: Protected field clear

NO_2:

Output signal 2 from the ESPE/AOPD (normally open 2)
NO_2 = 0: Protected field broken
NO_2 = 1: Protected field clear

GdOn:

Guard Only mode of ESPE/AOPD
GdOn = 0

Guard function of ESPE/AOPD is deactivated,
i.e. the ESPE/AOPD is switched off.

GdOn = 1

ESPE/AOPD is operating as a guarding device.

The signal can come from a connected operating mode
selector switch.

SB 069

AOPD_GDO

W- SSNR
X - GRP
X - NO_1
X - NO_2
X - GdOn
B - MTD
X - SSeq
X - ARSt
X - Test
X - RSET

ENBL -

X

TEST -

X

PWR

-

X