Modular Block System: Hydraulic Presses

Standard Function Blocks

SB066

• If there has been a fault, this must first be rectified before proceeding as

follows:
- If the gate is open, close the gate and reset via the reset button (

Strt).

If error bit 09 occurs (synchronisation time exceeded), close, open and
then close the gate again, then reset via the reset button (

Strt).

- If the gate is closed, open and close the gate and reset via the reset

button (

Strt).

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of DB015 (1st data block), until the fault has been fully dealt

with.

• Error messages in DB015

- Bit 08:

Function test not carried out (gate open/closed)
Remedy: Carry out function test and/or check switch, cable
and input card and then reset (input parameter

Strt)

- Bit 09:

S1 and S2 synchronisation time exceeded
Remedy: Check switch, cable and input card, carry out a
function test and then reset (input parameter

Strt)

- Bit 10:

Gate open (S1 open)
Remedy: Close gate, check switch, cable and input card and
then reset (input parameter

Strt)

- Bit 11:

Gate open (S2 open)
Remedy: Close gate, check switch, cable and input card and
then reset (input parameter

Strt)

- Bit 12:

Gate closed, S1 was not open
Remedy: Open gate, check switch, cable and input card and
then carry out function test and reset (input parameter

Strt)

- Bit 13:

Gate closed, S2 was not open
Remedy: Open gate, check switch, cable and input card, carry
out a function test and then reset (input parameter

Strt)