Standard Function Blocks

Modular Block System: Hydraulic Presses

SB065

FBL

SB065 is used in applications up to category 4. The function range of
SB065 corresponds largely to that of SB067. However, the value range for
the safety subroutine number SSNR has been expanded to 1...600 (see
Chapter 5, section entitled “Input parameter SSNR”).

Other changes compared with SB067:

• Additional input parameter to set the time for monitoring the feedback

loop individually

• Additional output parameter to drive 2 contactors

• Improved error message output

This standard function block is suitable for applications with SafetyBUS p.
It has an input parameter to evaluate the status of the I/O-Group
(SafetyBUS p), for which parameters are set on the feedback loop
contacts.

The use of SB065 is preferred in the following applications:

• Applications with SafetyBUS p

• Very extensive applications (> 200 standard function blocks) with/without

SafetyBUS p

In this case, a fast PSS-CPU (e.g. CPU 3) is also preferable.

Initialising the administration data blocks

SB070

INIT_MBS

SB070 exclusively initialises administration data block DB015 with global
parameters. For this reason it can only be used in applications which:

• Comprise a maximum of 200 standard function blocks

• Do not use standard function blocks SB063, SB064, SB065, SB069 and

SB075