8-32

Examples

Modular Block System: Hydraulic Presses

Safety gate monitoring with manual start and manual restart,
category 4

Block used: SB066/ST_K4

Cyclical function test on the gate:
The following application does not require a cyclical function test on the
gate.
However, should you wish to use this function you should assign the
“Machine running” signal to the input parameter

MEin.

Set operating mode:
The following operating mode is set for this application:

ARSt = 0: Reset lock activated (manual restart)

The operator must reset each time the safety gate opens
(input parameter

Strt).

NFkT = 1

No function test on safety gate when PSS starts up/resets

AuSt = 0

Reset disabler activated (manual start)
The operator must reset each time the PSS is started up or
restarted (input parameter

Strt).