Page 139

Advertising
background image

Modular Block System: Hydraulic Presses

6-77

- Bit 08:

Protected field broken
Remedy: Clear protected field, reset if necessary
Otherwise: Check ESPE/AOPD outputs, cable, input card and
all conditions and then reset (input parameter

RSET)

- Bit 09:

Start-up disabler
Remedy: Carry out a function test on the ESPE/AOPD (break
protected field and then clear) and then reset (input parameter
RSET)

- Bit 10:

I/O-Group stop triggered while PSS is in normal RUN mode
Remedy: Start I/O-Group

• Error messages on the CPU-display

- E003:

Administration data block has not been initialised
Remedy: Call SB071 in OB120

Global parameters used in the administration data blocks

Global parameters may be set in OB120 using SB071.

• DW1001:

Number of cycles in the contact synchronisation time

between two N/O or N/C contacts

• DW1022:

Minimum scan time

Blocks required

• DB015, DB016, DB017:

Administration data blocks
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.

• SB071

Initialisation of global parameters in DB015, DB016 and DB017