6-60

Modular Block System: Hydraulic Presses

Standard Function Blocks

SSeq:

The input parameter

SSeq establishes the start-up sequence:

- for the PSS start-up in “Guard only” mode (

GdO = 1) -

for changing the operating mode from “Aus” (

OFF = 1) to

“Guard only” (

GdO = 1)

- for 0/1-pulse edge at input parameter

RUN in “Guard only”

mode (

GdO = 1)

SSeq = 0:

No automatic start-up (start-up disabler)
Function test required: break the protected field,
clear it and then press the reset button (input
parameter

RSET). See section entitled “Function”.

SSeq = 1:

No automatic start-up (start-up disabler)
No function test required
Reset required (input parameter

RSET)

In cycle mode (single or double break), the start-up procedure
is established via the input parameter

STyp (see input

parameter

STyp).

INFORMATION
SSeq = RLO-0 (M110.00) must be set on presses.

ARSt:

Automatic restart after fault: “Protected field broken”
ARSt = 0:

After fault: “Protected field broken”, no automatic
restart once the protected field is clear
i.e. after the protected field is broken, a reset lock
will become active

ARSt = 1:

Automatic restart after fault “Protected field
broken”
i.e. once the protected field is broken and then
cleared, the reset lock is automatically reset.

DANGER!
The reset lock must always be activated on presses. For this
reason you should always set

ARSt = RLO-0 (M 110.00) if

your application does not require access to the protected field
outside the potentially dangerous movement.

ARSt may be

assigned a signal that is always set at a static “0” during the
potentially dangerous movement, and is only set to “1” outside
this movement.