Modular Block System: Hydraulic Presses
Standard Function Blocks
SB072
Switch conditions
“Muting ON”
Muting signals MP1 and MP2 must be operated consecutively. The
maximum value for the synchronisation time between the MP1 and MP2
signals is: t = TPSy (input parameter
TPSy).
“Muting OFF”
The switch condition for “Muting OFF” is fulfilled when input parameter:
- MP1 = 0 and
- MP2 = 0 and
- the ESPE/AOPD is released for the time t > interrupt time (input
parameter
TInt) or
- the ESPE/AOPD is released and there are no more muting signals (i.e.
MS1/MS2).
“Muting Start-Up”
Muting signals MP1 or MP2, or MS2, must be operated if a vehicle is
within the range of the ESPE/AOPD.