Blocks required – Pilz PSS SB HYD, Basic license User Manual
Page 115
Modular Block System: Hydraulic Presses
6-53
- Bit 14:
Strt input constantly high or set too early
Remedy: If
Strt input was not set too early and is constantly
high: Check switch, cable and input card, then reset (input
parameter
Strt).
If
Strt input was set too early: reset again
(input parameter
Strt)
- Bit 15:
Gate closed,
Strt signal is missing
Remedy: Check all conditions and then reset
(input parameter
Strt)
• Error messages on the CPU-display
- None
Global parameters used in administration data block DB015
Global parameters may be set in OB120 using SB070.
• DW1022: Minimum scan time
Blocks required
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
• SB070
Initialisation of global parameters in DB015