Examples – Pilz PSS SB HYD, Basic license User Manual

Page 276

Advertising
background image

8-40

Examples

Modular Block System: Hydraulic Presses

ESPE/AOPD in guard mode with automatic function test (SB068)

Block used: SB068/BWS_AOS

Set operating mode:
The following operating mode is set for this application:

OFF

= 0

ESPE/AOPD has guard function and reset lock

GdO

= 1

(Guard Only)

SBrk

= 0

The signal must come from a connected operating mode

DBrk

= 0

selector switch block (e.g. SB 051).

SSeq

= 0

Start-up disabler / function test

ARSt

= 0

Reset lock

Automatic test in guard-only mode:
The input parameter

Test should be assigned the enable signal (UN-

signal). With eccentric presses, this input should be assigned the output
parameter

UN from SB074, for example.

Sequence:
• Test input (input parameter

Test) = 0/1-pulse edge change at UN signal.

A change in the pulse edge at the UN signal activates the automatic test
of the ESPE/AOPD in each cycle.

• SB068 detects the change in the pulse edge

SB068 detects the change in the pulse edge at the test input and sets
the test output (output parameter

TEST) from a 1-signal to a 0-signal.

This switches off the ESPE/AOPD's emitter (test start).

• ESPE/AOPD's emitter switched off (significance)

Switching off the ESPE/AOPD's emitter simulates access into the
protected field. The ESPE/AOPD must react to this simulated access
(refer also to “Global parameter DW 1006” in Chapter 4).

• Reaction of the ESPE/AOPD

Both the N/O contacts on the ESPE/AOPD (input parameter

NO_1 and

NO_2) must change from a 1-signal to a 0-signal. As soon as both input
parameters

(NO_1 and NO_2) show a 0-signal, the ESPE/AOPD's

emitter will be switched back on via the test output (output parameter
TEST: 0/1-pulse edge).
The block enable output parameter

ENBL will go to a 0-signal (no block

enable).