Modular Block System: Hydraulic Presses

6-37

Example 1:
Parameters

ARSt, AuSt and NoFT = 0

These settings mean that the “start-up disabler” and “reset lock” functions
are activated; a function test of the gate is required.

With PSS cold or warm start (start-up disabler), proceed as follows:

- If the gate is open, close, open and then close the gate again, then

reset via the reset button (

RSET).

- If the gate is closed, open and close the gate and reset via the reset

button (

RSET).

• Subsequent statuses only after enable is issued (reset lock):

- If the gate is open, close the gate and reset via the reset button

(

RSET).

- If the gate is closed, reset via the reset button (

RSET).

• If there has been a fault, this must first be rectified before proceeding as

follows:
- If the gate is open, close the gate and reset via the reset button

(

RSET). If error bit 09 occurs (synchronisation time exceeded), close,

open and then close the gate again, then reset via the reset button
(

RSET).

- If the gate is closed, open and close the gate and reset via the reset

button (

RSET).

Example 2:
Parameters

ARST and AuST = 0, NoFT = 1

These settings mean that the “start-up disabler” and “reset lock” functions
are activated and a function test of the gate is not required.
• With PSS cold or warm start (start-up disabler), proceed as follows:

- If the gate is open, close the gate and reset via the reset button

(

RSET).

- If the gate is closed, reset via the reset button (

RSET).

• Subsequent statuses only after enable is issued (reset lock):

- If the gate is open, close the gate and reset via the reset button

(

RSET).

- If the gate is closed, reset via the reset button (

RSET).