Modular Block System: Hydraulic Presses
6-37
Example 1:
Parameters
ARSt, AuSt and NoFT = 0
These settings mean that the “start-up disabler” and “reset lock” functions
are activated; a function test of the gate is required.
•
With PSS cold or warm start (start-up disabler), proceed as follows:
- If the gate is open, close, open and then close the gate again, then
reset via the reset button (
RSET).
- If the gate is closed, open and close the gate and reset via the reset
button (
RSET).
• Subsequent statuses only after enable is issued (reset lock):
- If the gate is open, close the gate and reset via the reset button
(
RSET).
- If the gate is closed, reset via the reset button (
RSET).
• If there has been a fault, this must first be rectified before proceeding as
follows:
- If the gate is open, close the gate and reset via the reset button
(
RSET). If error bit 09 occurs (synchronisation time exceeded), close,
open and then close the gate again, then reset via the reset button
(
RSET).
- If the gate is closed, open and close the gate and reset via the reset
button (
RSET).
Example 2:
Parameters
ARST and AuST = 0, NoFT = 1
These settings mean that the “start-up disabler” and “reset lock” functions
are activated and a function test of the gate is not required.
• With PSS cold or warm start (start-up disabler), proceed as follows:
- If the gate is open, close the gate and reset via the reset button
(
RSET).
- If the gate is closed, reset via the reset button (
RSET).
• Subsequent statuses only after enable is issued (reset lock):
- If the gate is open, close the gate and reset via the reset button
(
RSET).
- If the gate is closed, reset via the reset button (
RSET).