6-166

Modular Block System: Hydraulic Presses

Standard Function Blocks

SB097

Wiring the output parameters

Positive or negative-switching outputs can be used to drive the muting
lamps.
If positive-switching outputs are used, muting lamps must be switched with
the aid of optocouplers (e.g. PHOENIX power couplers, type ST-0V-2, Art.
No. 29 05 49 1, 24 VDC/24 VDC 5 A).
With negative-switching outputs (e.g. output xx.06 and xx.07 on the
SafetyBUS p module PSS SB DI8O8), the muting lamps can be switched
directly.
See example: “Monitoring muting lamps” in Chapter 8.

Wiring diagram

Function

The block uses feedback inputs (input parameters

FbL1 / FbL2) to monitor

the filaments on two muting lamps (output parameters

LMP1 / LMP2).

Monitoring occurs in both the off state (input parameter

ON = 0) and the

on state (input parameter

ON = 1). In the off state, 1-Potential must be

present at the feedback input. In the on state, the output through which the
muting lamp is driven will be switched off and checked. This happens
every 12 seconds; the time is not adjustable. If the filament is in order,
1-potential is present at the feedback input. If the filament has blown, 0-
potential will be present.

24 V DC

Positive-

switching

output

LMP1

Input

FbL1

Input

FbL2

Positive-

switching

output

LMP2

0 V DC

Fig. 6-9: Wiring diagram