Output parameters, Function test – Pilz PSS SB HYD, Basic license User Manual

Page 91

Advertising
background image

Modular Block System: Hydraulic Presses

6-29

AuSt = 1: No initial reset required
Sequence: When the PSS is cold/warm started or the I/O-
Group is started (GRP = 0/1-pulse edge), the enable is
triggered without a further initial reset.

NC_1 = 1 und NC_2 = 1

is also required in order to set the enable.

ARSt:

Automatic reset when E-STOP button is released
ARSt = 0: Reset through input parameter RSET is required
ARSt = 1: Automatic reset required when E-STOP button is
released

FTST

Function test
FTST = 0: No function test required
FTST = 1: A function test must be performed if a
synchronisation error occurs when the E-STOP button is
released.

RSET:

Reset button (N/O contact)
RSET = 0/1-pulse edge: Reset occurs
RSET should be assigned RLO-0 if you do not need a reset
button (e.g. with automatic reset).

Output parameters

ENBL:

Enable bit
ENBL = 0: Enable is blocked
ENBL = 1: This function is error-free, the E-STOP button

has not been operated

Function test

The function test will check whether both contacts on the E-STOP button
are switching synchronously.
A function test must always be performed if a synchronisation error occurs
when the E-STOP button is operated.
Input parameter

FTST can be used to establish whether or not a function

test is required if a synchronisation error occurs when the E-STOP button
is released.