Standard function blocks, Sb088 – Pilz PSS SB HYD, Basic license User Manual

Page 202

Advertising
background image

6-140

Modular Block System: Hydraulic Presses

Standard Function Blocks

maximum time (reaction time). The maximum reaction time when
switching on the valves can be set via the input parameter

TOn (for

both valves). If the maximum reaction time is exceeded, an error
message will be issued (output parameter

ENBL = 0 and ERR = 1) and

the valves will switch off immediately (output parameter

Y1 = 0 and

Y2 = 0). A reset will be necessary (see also under “Error messages”).

- Reaction time when switching off the valve:

When switched off, the valves must reach their start position within a
maximum time (reaction time). The maximum reaction time when
switching off the valves can be set via the input parameter

TOff (for

both valves). If the maximum reaction time is exceeded, an error
message will be issued (output parameter

ENBL = 0 and ERR = 1) and

a reset will be necessary (see also under “Error messages”).

INFORMATION
SB088 is designed for dual valves. You can assume that these will have
a similar switching characteristic. This means that the reaction time for
switching on (off) both valves can be monitored through the input
parameters

TOn (TOff).

• Position is monitored via acknowledgement of the valve's position (input

parameters

S1 and S2), without setting a maximum reaction time (input

parameter

TOn = 0 and TOff = 0).

When monitoring the position of a valve without monitoring the reaction
time, SB088 checks that the valves leave their start position (valve de-
energised, acknowledgement present) at least once in each working
cycle (valve switching on and off). If this is not the case, SB088 will
register an error (output parameter

ENBL = 0 and ERR = 1) and the

valves will switch off immediately (output parameter

Y1 = 0 and Y2 = 0).

A reset will be necessary (see also under “Error messages”).

• Monitoring the position of directional control valves

With directional control valves, the position of the valves is monitored as
they are being operated. The valves must not register their start position
while they are being operated. If the directional control valves are
correctly energised (input parameter

ON = 1) and their start position is

registered while the valve output is switched on (output parameter

Y1 =

1 and

Y2 = 1), SB088 immediately switches off the valve output (output

parameter

Y1 = 0 and Y2 = 0) and registers a fault (output parameter

ENBL = 0 and ERR = 1). A reset will be necessary (see also under
“Error messages”).

SB088