Sb061: emergency stop monitoring, category 4, Block header, Input parameters – Pilz PSS SB HYD, Basic license User Manual

Page 86: Standard function blocks, Sb061

Advertising
background image

6-24

Modular Block System: Hydraulic Presses

Standard Function Blocks

SB061: Emergency stop monitoring, category 4

Block header

Input parameters

SSNR:

Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).

EIN:

Reset button (N/O contact)
EIN = 0/1-pulse edge: Reset occurs

S1_Ö :

E-STOP N/C contact 1

S2_Ö :

E-STOP N/C contact 2

QAnf:

Automatic reset (PSS cold start)
QAnf = RLO-0 (M 110.00): No reset required.

Cycle: When the PSS is started up or cold started,
the enable is triggered without an additional reset.

QAnf = RLO-1 (M 110.01): Reset required.

Cycle: When the PSS is started up or cold
started, a reset is required through the input
parameter

EIN in order to trigger the enable.

QAut:

Automatic reset when E-STOP button is released
QAut = 0:

Reset through input parameter

EIN is required.

SB 061

NA_1

B - SSNR
X - EIN
X - S1_Ö
X - S2_Ö
X - QAnf
X - QAut

FG - X

SB061