Sb061: emergency stop monitoring, category 4, Block header, Input parameters – Pilz PSS SB HYD, Basic license User Manual
Page 86: Standard function blocks, Sb061
6-24
Modular Block System: Hydraulic Presses
Standard Function Blocks
SB061: Emergency stop monitoring, category 4
Block header
Input parameters
•
SSNR:
Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).
•
EIN:
Reset button (N/O contact)
EIN = 0/1-pulse edge: Reset occurs
•
S1_Ö :
E-STOP N/C contact 1
•
S2_Ö :
E-STOP N/C contact 2
•
QAnf:
Automatic reset (PSS cold start)
QAnf = RLO-0 (M 110.00): No reset required.
Cycle: When the PSS is started up or cold started,
the enable is triggered without an additional reset.
QAnf = RLO-1 (M 110.01): Reset required.
Cycle: When the PSS is started up or cold
started, a reset is required through the input
parameter
EIN in order to trigger the enable.
•
QAut:
Automatic reset when E-STOP button is released
QAut = 0:
Reset through input parameter
EIN is required.
SB 061
NA_1
B - SSNR
X - EIN
X - S1_Ö
X - S2_Ö
X - QAnf
X - QAut
FG - X
SB061