Transport vehicle danger area – Pilz PSS SB HYD, Basic license User Manual

Page 155

Advertising
background image

Modular Block System: Hydraulic Presses

6-93

Sequential muting mode
(Muting when entering the danger area)

Fig. 6-1: Entering the danger area (sequential muting mode)

Muting signal arrangement

Position MS1/MS2 and distance A/B:

Distance B should be as long as possible, but shorter than the
length of transport vehicle W.
Required: W > B and W > A

Position MS2 and distance C:

MS2 must be located as close as possible to the ESPE/AOPD,
i.e. distance C should be as short as possible.

Position MP1:

Requires muting signal MP1.

Position MP2:

Muting signal MP2 is optional and is used to detect vehicles
leaving the danger area (please refer to “Parallel mode”).
If the muting signal MP2 is used, it must be operated at the
same time as MP1.
If muting signal MP2 is not being used, the input parameter
MP2 should be assigned RLO-0 (M 110.00).

MS1

MS2

MP2

ESPE/

AOPD

MP1

ESPE/

AOPD

W

B

C

C

A

Transport

Vehicle

Danger Area