Watson-Marlow MM420 User Manual

Page 111

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

111

mandatory to parameterize for a variable word length, if e.g. all values are to be
read at once from an “indexed” parameter (refer to "Index", special setting, index =
255). This setting to variable word-length is made during start-up. (refer to
parameter P2013).

Parameter ID (PKE)

1

st

word

15

14

13 12

11

10 9 8 7 6 5 4 3 2 1 0

Bit No.:

AK

SP

M

PNU1

Parameter index (IND)

2

nd

word

15

14

13 12

11

10 9 8 7 6 5 4 3 2 1 0

Bit No.:

PNU2 RES

TXT

Index

Parameter value (PWE)

15

14

13 12

11

10 9 8 7 6 5 4 3 2 1 0

Bit No.:

Parameter value, high

(PWE1)

3

rd

word

Parameter value, low

(PWE2)

4

th

word


The following applies:

AK

Task or reply ID

SPM

Toggle bit for processing of parameter-change reports
(MICROMASTER does not support this, SPM = 0)

PNU

Parameter number

RES

Reserved

TXT

Read / write from parameter text
(MICROMASTER does not support this, TXT = 0)

CAUTION

Do not use a variable word length if SIMATIC S5 or SIMATIC S7 is the master.
This setting must be made both at the master as well as at the slave – and

cannot be changed while the bus is operational.


NOTE

The PKW area is transferred in increasing order, always starting with the 1st

word.

Reserved fields or functions that are not supported should be specifically pre-

assigned zero in the master implementation.

The bit 11 (SPM) is the toggle bit for parameter change reports. Parameter

change reports when reading/writing parameter texts are not supported by
MICROMASTER.