3 Functions

Issue 10/06

MICROMASTER 420 Operating Instructions

68

6SE6400-5AA00-0BP0

Table 3-8

Example 1LA7060-4AB10

Delta

circuit

configuration

87 Hz

characteristic

Star circuit

configuration

P0304

Rated motor voltage

230 V

400 V

400 V

P0305

Rated motor current

0.73 A

0.73 A

0.42 A

P0307

Rated motor power

120 W

207 W

120 W

P0308

Cos

ϕ

0.75 0.75 0.75

P0310

Rated motor frequency

50 Hz

87 Hz

50 Hz

P0311

Rated motor speed

1350 RPM

2460 RPM

1350 RPM

P0314

Motor pole pairs

2

2

2

Contrary to the BOP, AOP operator panels or commissioning tool program
DriveMonitor, the STARTER commissioning (start-up) program offers a mask-
orientated quick commissioning, which is especially advantageous for users who
are using MICROMASTER for the first time. On the other hand, BOP, AOP and
DriveMonitor offer, in conjunction with the drive inverter, parameter-orientated
quick commissioning where the user is navigated through the menu tree mentioned
above.

NOTE
The MICROMASTER series of drive units is not available for 3-ph. 690 V AC.