5 MICROMASTER 420 specifications

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

185

Table 5-2

Dimensions, required cooling air flow and tightening torques for power terminals

Frame

Size

Dimensions

Required cooling air

flow

Tightening torque for

power connections

mm

73

× 173 × 149

l/s 4.8

Nm 1.1

A

W x H x D

inch

2.87

× 6.81 × 5.87

CFM 10.2

lbf.in

10

mm

149

× 202 × 172

l/s 24

Nm 1.5

B

W x H x D

inch

5.87

× 7.95 × 6.77

CFM 51

lbf.in

13.3

mm

185

× 245 × 195

l/s 54.9 Nm 2.25

C

W x H x D

inch

7.28

× 9.65 × 7.68

CFM 116.3

lbf.in

20

Table 5-3

Current reduction depending on pulse frequency

Output current in A with a switching frequency of:

Mains voltage Power (CT)

[kW]

4 kHz

6 kHz

8 kHz

10 kHz

12 kHz

14 kHz

16 kHz

1/3 AC 200 V

0.12 to 5.5 Factory setting 16 kHz – no derating necessary

0.37 1.2 1.2 1.2 1.2 1.2 1.2 1.1

0.55 1.6 1.6 1.6 1.6 1.6 1.6 1.1

0.75 2.1 2.1 2.1 2.1 1.6 1.6 1.1

1.1 3.0 3.0 2.7 2.7 1.6 1.6 1.1

1.5 4.0 4.0 2.7 2.7 1.6 1.6 1.1

2.2 5.9 5.9 5.1 5.1 3.6 3.6 2.6

3.0 7.7 7.7 5.1 5.1 3.6 3.6 2.6

4.0 10.2 10.2 6.7 6.7 4.8 4.8 3.6

5.5 13.2 13.2 13.2 13.2 9.6 9.6 7.5

7.5 19.0 18.4 13.2 13.2 9.6 9.6 7.5

3 AC 400 V

11.0 26.0 26.0 17.9 17.9 13.5 13.5 10.4