20 power module protection, 1 general overload monitoring – Watson-Marlow MM420 User Manual

Page 164

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 420 Operating Instructions

164

6SE6400-5AA00-0BP0

3.20

Power module protection

3.20.1

General overload monitoring

Parameter range:

P0640, r0067, r1242, P0210

Warnings

A0501, A0502, A0503

Faults

F0001, F0002, F0003

Function chart number:

-

Just the same as for motor protection, MICROMASTER provides extensive
protection for the power components. This protection concept is also sub-divided
into 2 levels:

Warning and response
Fault and shutdown

Using this concept, a high utilization of the power module components can be
achieved without the drive inverter being immediately shut down. The power
module components are monitored as follows:

Table 3-33

General protection of the power components

Warning and response

Fault and shutdown

Overcurrent / short circuit

Imax controller for V/f

A0501

r0056 bit 09
r0056 bit 13

(refer to Section 3.21.1.2)

F0001




DC link overvoltage

Vdc_max controller

A0502

(refer to Section 3.17.1)

F0002


The monitoring thresholds for the right-hand column in the table above are
permanently saved in the drive inverter and cannot be changed by the user. On the
other hand, the threshold levels for the "Warning and response" column can be
modified by the user to optimize the system. These values have default settings so
that the "Fault and shutdown" thresholds do not respond.