2 quick commissioning – Watson-Marlow MM420 User Manual

Page 62

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 420 Operating Instructions

62

6SE6400-5AA00-0BP0

By changing the setting of 50/60 Hz DIP switch, after the drive inverter has been
powered-down/powered-up, the parameters for the rated motor frequency P0310,
max. frequency P1082 and reference frequency P2000 are automatically pre-set.
In addition, the rated motor parameters as well as all of the other parameters which
depend on the rated motor parameters, are reset. The units of the power
parameters are, depending on P0100, are either interpreted as kW value or hp
value.

3.5.2 Quick

commissioning

If there is still no appropriate parameter set for the drive, then a quick
commissioning must be carried-out including a motor data identification routine.
The following operator units can be used to carry-out quick commissioning:

BOP (option)
AOP (option)
PC Tools (with commissioning software STARTER, DriveMonitor)

When the quick commissioning is carried-out, the motor – drive inverter is basically
commissioned; the following data must be obtained, modified or entered before
quick commissioning is started:

Enter the line supply frequency
Enter the rating plate data
Command / setpoint sources
Min. / max. frequency or ramp-up / ramp-down time
Control mode
Motor data identification

Parameterizing the drive with BOP or AOP

The frequency inverter is adapted to the motor using the quick commissioning
function and important technological parameters are set. The quick commissioning
shouldn't be carried-out if the rated motor data saved in the frequency inverter
(4-pole 1LA Siemens motor, star circuit configuration frequency inverter (FU)-
specific) match the rating plate data.

Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.

START



Factory setting

P0003 = 2

User access level *
1 Standard: Allows access into most frequently used parameters
2 Extended: Allows extended access e.g. to inverter I/O functions
3 Expert (For expert use only)

P0010 = 1

Commissioning parameter *
0 Ready
1 Quick commissioning
30 Factory

setting

NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.

0

1

Advertising