Watson-Marlow MM420 User Manual

Page 54

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 420 Operating Instructions

54

6SE6400-5AA00-0BP0

3.2.3

Keys and their functions on the operator panel (BOP / AOP)

Operator

panel/key

Function Effects

Indicates

Status

The LCD displays the settings currently used by the converter.

Start

converter

Pressing the button starts the converter. This button is disabled by default.
Activate the button:

BOP:

P0700 = 1 or P0719 = 10 ... 16

AOP: P0700 = 4 or P0719 = 40 ... 46

on BOP link

P0700 = 5 or P0719 = 50 ... 56

on COM link

Stop

converter

OFF1 Pressing the button causes the motor to come to a standstill at the

selected ramp down rate.
Activate the button: see button "Start converter"

OFF2 Pressing the button twice (or once long) causes the motor to coast to a

standstill.

BOP: This function is always enabled

(independent of P0700 or P0719).

Change

direction

Press this button to change the direction of rotation of the motor. Reverse is
indicated by a minus (-) sign or a flashing decimal point. Disabled by default.
Activate the button: see button "Start converter".

Jog motor

In the "Ready to power-on" state, when this key is pressed, the motor starts and
rotates with the pre-set jog frequency. The motor stops when the button is
released. Pressing this button when the motor is running has no effect.

Functions

This button can be used to view additional information.
It works by pressing and holding the button. It shows the following, starting from
any parameter during operation:
1. DC link voltage (indicated by d – units V).
2. output current. (A)
3. output frequency (Hz)
4. output voltage (indicated by o – units V).
5. The value selected in P0005 (If P0005 is set to show any of the above (1 - 4)

then this will not be shown again).

Additional presses will toggle around the above displays.
Jump Function
From any parameter (rxxxx or Pxxxx) a short press of the Fn button will
immediately jump to r0000, you can then change another parameter, if required.
Upon returning to r0000, pressing the Fn button will return you to your starting
point.
Acknowledgement
If alarm and fault messages are present, then these can be acknowledged by
pressing key Fn.

Access

parameters

Pressing this button allows access to the parameters.

Increase

value

Pressing this button increases the displayed value.

Decrease

value

Pressing this button decreases the displayed value.

+

AOP menu

Calls the AOP menu prompting (this is only available for AOP).

Fig. 3-9

Operator panel keys

Advertising