When the filter time constant P0753 (ADC-PT1) is increased, this smoothes the
ADC input signal therefore reducing the ripple. When this function is used within a
control loop, this smoothing has a negative impact on the control behavior and
immunity to noise (the dynamic performance deteriorates).

Wire breakage monitoring

The wire breakage monitoring (refer to Fig. 3-25) is set using parameters P0756
and P0761. If the input signal of the analog input falls below the wire breakage
threshold (0.5 * P0761), then after the time in P0762 expires, fault F0080 is output

and the status bit is set in parameter r0751.

t

0

Signal loss

t

0

P0761

V

1

P0761

0,5

10

P0762

r0751

t

0

1

F0080

Fault acknowl.

Analog input

t

0

Act. ADC after scaling
r0755

Fig. 3-26

Wire breakage monitoring

The following secondary conditions/limitations apply to the wire breakage
monitoring:

The monitoring function must be activated using parameter P0756
Width of the ADC dead zone P0761 > 0
Wire breakage monitoring if the ADC input quantity ≤ 0.5 * P0761

Note

The wire-breakage monitoring function is only possible for unipolar analog

inputs.

Input range 0 to 0.5 * P0761 of the analog input must be excluded when

activating the wire breakage monitoring for normal operation.