Watson-Marlow MM420 User Manual

Page 63

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

63

P0100 =...


P0100 = 1, 2



P0100 = 0

Europe/ North America
(enters the line supply frequency)
0 Europe [kW], frequency default 50 Hz
1 North America [hp], frequency default 60 Hz
2 North America [kW], frequency default 60 Hz
NOTE
For P0100 = 0 or 1, the setting of switch DIP2(2)
determines the value of P0100 (refer to the
parameter list).

50/60 Hz DIP switch
for frequency setting

60 Hz

50 Hz

P0304 =... P0304 =... Rated motor voltage

(Nominal motor voltage [V] from rating
plate)
The rated motor voltage on the rating
plate must be checked, regarding the
star/delta circuit configuration to ensure
that it matches with the circuit
connection configured at the motor
terminal board

P0305 =... P0305 =... Rated motor current

(Nominal motor current [A] from rating
plate)

P0307 =... P0307 =... Rated motor power

(Nominal motor power [kW/hp] from
rating plate)
If P0100 = 0 or 2, value will be in kW. If
P0100 = 1, value will be in in hp.

P0304

P0305

P0307

P0308 P0311

P0310

P0308 =...

P0308 =...

Rated motor cosPhi
(Nominal motor power factor (cos

ϕ) from rating plate)

If the setting is 0, the value is automatically calculated
P0100 = 1,2: P0308 no significance, no entry required.

P0309 =...

P0309 =... Rated motor efficiency

(Nominal motor efficiency in [%] from rating plate)
Setting 0 causes internal calculation of value.
P0100 = 0: P0309 no significance, no entry required.

P0310 =...

Rated motor frequency
(Nominal motor frequency in [Hz] from rating plate)
Pole pair number recalculated automatically if parameter is changed.

P0311 =...

Rated motor speed
(Nominal motor speed in [rpm] from rating plate)
Setting 0 causes internal calculation of value.
NOTE

For slip compensation, the input is absolutely necessary.

P0335 =...

Motor cooling

(Selects motor cooling system used)
0 Self-cooled: Using shaft mounted fan attached to motor
1 Force-cooled: Using separately powered cooling fan

P0640 =...

Motor overload factor

(Motor overload factor in [%] relative to P0305)
This defines the limit of the maximum output current as a % of the rated motor
current (P0305).

0

FU-spec.

FU-spec.

FU-spec.

FU-spec.

FU-spec.

50.00 Hz

FU-spec.

0

150 %

Advertising