10 jog – Watson-Marlow MM420 User Manual

Page 126

Advertising
background image

3 Functions

Issue 10/06

MICROMASTER 420 Operating Instructions

126

6SE6400-5AA00-0BP0

3.10 JOG

Parameter range:

P1055 – P1061

Warnings A0923
Faults -
Function chart number:

FP5000

The JOG function is used as follows:

To check the functionality of the motor and drive inverter after commissioning

has been completed (the first traversing motion, checking the direction of
rotation, etc.)

Positioning a drive / a driven load into a specific position
Traversing a drive, e.g. after a program has been interrupted

The drive is traversed using this function by entering fixed frequencies P1058,
P1059. The JOG mode can be selected either using the operator panel (refer to
Section 3.1.3), digital inputs or also via the serial interfaces (refer to the example).
An ON/OFF command is not used to move the drive, but when the "JOG keys" are
pressed. These "JOG keys" are selected using the BICO parameters P1055 and
P1056.

JOG right

f

P1058

P1059

A0923

A0923

P1

06

0

P1

06

0

(0)

P1055

(0)

P1056

"1"

"0"

"1"

"0"

t

t

t

P10

61

DIN

BOP

USS

BOP link

USS

COM link

CB

COM link

JOG left

P1082

-P1082

P1

06

1

Fig. 3-45

JOG counter-clockwise and JOG clockwise

Advertising