3 Functions

Issue 10/06

MICROMASTER 420 Operating Instructions

138

6SE6400-5AA00-0BP0

OFF2

The inverter pulses are immediately cancelled by the OFF2 command. This means
that the motor coasts-down and it is not possible to brake in a controlled fashion.

t

t

Pulse

cancellation

Operation

act

f

OFF2

P1082

f

max

r0052 Bit02

Fig. 3-55

OFF2

NOTE

The OFF2 command can have one or several sources. The command sources

are defined using BICO parameters P0844 (BI: 1. OFF2) and P0845 (BI: 2.
OFF2).

As a result of the pre-assignment (default setting), the OFF2 command is set to

the BOP. This source is still available even if another command source is
defined (e.g. terminal as command source

→ P0700 = 2 and OFF2 is selected

using DIN2

→ P0702 = 3).

OFF3

The braking characteristics of OFF3 are identical with those of OFF1 with the
exception of the autonomous OFF3 ramp-down time P1135. If the output frequency
falls below parameter value P2167 and if the time in P2168 has expired, then the
inverter pulses are cancelled as for the OFF1 command.

t

P2168

t

P2167

Operation

act

f

OFF3

P1082

f

max

r0052 Bit02

P1135

P1082

f

P1135

t

2

3

OFF

,

down

=

t

down,OFF3

Pulse

cancellation

Fig. 3-56

OFF3

NOTE
OFF3 can be entered using a wide range of command sources via BICO
parameters P0848 (BI: 1. OFF3) and P0849 (BI: 2. OFF3).