3 Functions

Issue 10/06

MICROMASTER 420 Operating Instructions

78

6SE6400-5AA00-0BP0

3.5.5.9

Fixed frequency (FF)

P1001 =...

Fixed frequency 1
Can be directly selected via DIN1
(P0701 = 15, 16)

P1002 =... Fixed frequency 2

Can be directly selected via DIN2
(P0702 = 15, 16)

P1003 =... Fixed frequency 3

Can be directly selected via DIN3
(P0703 = 15, 16)

P1004 =... Fixed frequency 4

P1005 =... Fixed frequency 5

P1006 =... Fixed frequency 6

P1007 =... Fixed frequency 7

When defining the function of the digital inputs
(P0701 to P0703), three different types can be
selected for fixed frequencies:
15 = Direct selection (binary-coded)

In this particular mode, the appropriate
digital input always selects the associated
fixed frequency, e.g.:
Digital input 3 = selects fixed frequency 3.
If several inputs are simultaneously active,
then these are summed. An ON command is
additionally required.

16 = Direct selection + ON command

(binary-coded + On / Off1)
In this mode, the fixed frequencies are
selected as for 15, however these are
combined with an ON command.

17 = Binary coded selection + ON command

(BCD-coded + On/ Off1)
The BCD-coded operating mode is effective
for digital inputs 1 to 3.

P1016 =... Fixed frequency code –

Bit 0

Defines the selection method for fixed
frequencies.

P1017 =... Fixed frequency code –

Bit 1

P1018 =... Fixed frequency code –

Bit 2

1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
NOTE
For settings 2 and 3, all parameters P1016 to
P1019 must be set to the selected value so that
the drive inverter accepts the ON command.

3.5.5.10 JOG

P1058 =...

JOG frequency right
Frequency in Hz when the motor is being
jogged in the clockwise direction of rotation.

P1059 =...

JOG frequency left
Frequency in Hz when the motor is being
jogged in the counter-clockwise direction of
rotation.

P1060 =...

JOG ramp-up time
Ramp-up time in s from 0 to the maximum
frequency (P1082). The JOG ramp-up is
limited by P1058 or P1059.

P1061 =...

JOG ramp-down time
Ramp-down time in s from the maximum
frequency (P1082) to 0.

P1082
(f

max

)

P1058

t

P1060

P1061

f

JOG

5.00 Hz

10.00 Hz

15.00 Hz

20.00 Hz

25.00 Hz

30.00 Hz

0.00 Hz

1

1

1

10.00 s

10.00 s

5.00 Hz

5.00 Hz