Watson-Marlow MM420 User Manual

Page 65

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

65

P3900 = 1

End of quick commissioning

(start of the motor calculation)
0 No quick commissioning (no motor calculations)
1 Start quick commissioning with factory reset
2 Start quick commissioning
3 Start quick commissioning only for motor data

NOTE
For P3900 = 1,2,3

→ P0340 is internally set to 1 and the appropriate data

calculated (refer to the parameter list P0340).

ENDE

End of quick commissioning/ drive setting

If additional functions must be implemented at the drive inverter, please use the
instructions in Section 3.5.5 "Commissioning the application". We recommend this
procedure for drives with a high dynamic response..



WARNING
The motor data identification routine (refer to Section 3.5.4) may not be used for
loads which are potentially hazardous (e.g. suspended loads for crane
applications). Before the motor data identification run is started, the potentially
hazardous load must be carefully secured (e.g. by lowering the load to the floor or
by clamping the load using the motor holding brake).

NOTE

The precise equivalent circuit diagram data are extremely important for the

voltage boost of the V/f characteristic. The equivalent diagram data can only be
estimated from the rating plate data. This is the reason that the equivalent
circuit diagram data are, either
- determined using the motor data identification routine (refer to Section 3.5.4),
or
- entered from the motor data sheet (refer to Section 3.5.3).

Parameter P0308 or P0309 are only visible using the BOP or AOP if P0003

≥ 2.

Depending on the setting of parameter P0100, either P0308 or P0309 is
displayed.

The input value of P0307 and all other power data are either interpreted as kW

or hp value depending on P0100.

The possible rating plate / power plate data is shown in Fig. 3-17. The precise
definition and explanation of this data is defined in DIN EN 60 034-1.

Fig. 3-17

Example of a typical motor rating plate