11 ramp-function generator (hlg) – Watson-Marlow MM420 User Manual

Page 79

Advertising
background image

Issue 10/06

3 Functions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

79

3.5.5.11

Ramp-function generator (HLG)

P1091 =...

Skip frequency 1

(entered in Hz)

Defines skip frequency 1 which avoids
effects of mechanical resonance and
suppresses frequencies within +/- P1101
(skip frequency bandwidth).

P1091 =...

Skip frequency 2

P1091 =...

Skip frequency 3

P1091 =...

Skip frequency 4

P1101 =...

Skip frequency bandwidth
(entered in Hz)

P1101

P1091

f

in

f

out

Skip frequency

bandwidth

Skip frequency

P1120 =...

Ramp-up time
(enters the accelerating time in s)

P1121 =...

Ramp-down time
(enters the deceleration time in s)

f

P1082
(f

max

)

f

1

t

P1120

P1121

P1130 =...

Rump-up initial rounding time
(entered in s)

P1131 =...

Ramp-up final rounding time
(entered in s)

P1132 =...

Rump-down initial rounding time
(entered in s)

P1133 =...

Ramp-down final rounding time
(entered in s)

P1134 =...

Rounding type
0 Continuous smoothing
1 Discontinuous smoothing

The rounding times are recommended as
abrupt responses can be avoided therefore
reducing stress and damage to the mechanical
system.
The ramp-up and ramp-down times are
extended by the component of the rounding
ramps.

P1135 =...

OFF3 ramp-down time

Defines ramp-down time from maximum frequency to standstill for OFF3 command.

2.00 Hz

0.00 Hz

0.00 Hz

0.00 Hz

0.00 Hz

10.00 s

10.00 s

5.00 s

0.00 s

0

0.00 s

0.00 s

0.00 s

Advertising