Watson-Marlow MM420 User Manual

Page 187

Advertising
background image

Issue 10/06

5 MICROMASTER 420 specifications

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

187

Input voltage range

1 AC 200 V – 240 V, ± 10 %

(Unfiltered)

Order No.

6SE6420- 2UC11

-2AA1

2UC12

-5AA1

2UC13

-7AA1

2UC15

-5AA1

2UC17

-5AA1

2UC21

-1BA1

2UC21

-5BA1

2UC22

-2BA1

2UC23

-0CA1

[kW] 0.12 0.25 0.37 0.55

0.75 1.1 1.5 2.2 3.0

Output Rating

[hp] 0.16 0.33 0.5

0.75 1.0 1.5 2.0 3.0 4.0

Output Power

[kVA]

0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0

Input

Current

1)

[A] 1.8 3.2 4.6 6.2 8.2 11.0 14.4 20.2 35.5

Output

Current

[A] 0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4 13.6

Fuse

[A] 10 10 10 10 16 20 20 32 40

Recommended

3NA 3803 3803 3803 3803 3805 3807 3807 3812 3817

For UL specified

* * * * * * * * *

[mm

2

] 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.5

Input Cable, min.

[awg] 18 18 18 18 18 18 18 18 14

[mm

2

]

2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0

Input Cable, max.

[awg] 14 14 14 14 14 10 10 10 8

[mm

2

]

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5

Output Cable, min.

[awg] 18 18 18 18 18 18 18 18 16

[mm

2

]

2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0

Output Cable, max.

[awg] 14 14 14 14 14 10 10 10 8

[kg] 1.2 1.2 1.2 1.2 1.2 2.9 2.9 3.1 5.2

Weight

[lbs] 2.6 2.6 2.6 2.6 2.6 6.4 6.4 6.8

11.4

Input voltage range

3 AC 200 V – 240 V, ± 10 %

(with built in Class A Filter)

Order No.

6SE6420- 2AC23

-0CA1

2AC24

-0CA1

2AC25

-5CA1

[kW] 3.0 4.0 5.5

Output Rating

[hp] 4.0 5.0 7.5

Output Power

[kVA]

6.0

7.7

9.6

Input Current 1)

[A]

15.6 19.7 26.5

Output Current

[A]

13.6

17.5

22.0

Fuse [A]

25 32 35

Recommended

3NA

3810

3812

3814

For UL specified

* * *

[mm

2

] 2.5 2.5 4.0

Input Cable, min.

[awg] 14 14 12

[mm

2

] 10.0 10.0 10.0

Input Cable, max.

[awg] 8 8 8

[mm

2

] 1.5 2.5 4.0

Output Cable, min.

[awg] 16 14 12

[mm

2

] 10.0 10.0 10.0

Output Cable, max.

[awg] 8 8 8

[kg] 5.2 5.5 5.5

Weight

[lbs] 11.4 12.1 12.1

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 2 % referred to the rated drive converter power and a rated line supply voltage

of 240 V without line commutating reactor.

* UL listed fuses such as Class NON from Bussmann are required for use in America

Advertising