2 power and motor connections – Watson-Marlow MM420 User Manual

Page 29

Advertising
background image

Issue 10/06

2 Installation

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

29

2.4.2

Power and motor connections

WARNING

The inverter must always be grounded

.

♦ Isolate the mains electrical supply before making or changing connections to

the unit.

♦ Ensure that the motor is configured for the correct supply voltage: single /

three-phase 230 V MICROMASTERS must not be connected to a 400 V
three-phase supply.

♦ When synchronous motors are connected or when coupling several motors in

parallel, the inverter must be operated with voltage/frequency control
characteristic (P1300 = 0, 2 or 3).

CAUTION
After connecting the power and motor cables to the proper terminals, make sure
that the covers have been replaced properly before supplying power to the unit!

NOTICE
♦ Ensure that the appropriate circuit-breakers/fuses with the specified current

rating are connected between the power supply and inverter (see chapter 5,
Tables starting on page 186).

♦ Use Class 1 60/75

o

C copper wire only (for UL compliance). For tightening

torque see Table 5-2, page 185.

Operation with long cables

All inverters will operate at full specification with cable lengths up to 50 m screened
or 100 m unscreened.
When using output reactors as shown in Catalog DA 51.2, the following cable
lengths are possible:

Supply Voltage

200 V … 240 V ± 10 %

380 V … 400 V ± 10 %

401 V … 480 V ± 10 %

Frame Sizes

A … C

A … B

C

A … C

Shielded

200 m

150 m

200 m

100 m

Non-shielded

300 m

225 m

300 m

150 m

CAUTION
When using output reactors and LC filters, operation up to a pulse frequency of 4
kHz

only is permitted. Please ensure that the automatic pulse frequency reductions

are also deactivated. Mandatory parameter settings when using an output reactor:
P1800 = 4 kHz , P0290 = 0 or 1

.