Safety Instructions

MICROMASTER 420 Operating Instructions

6SE6400-5AA00-0BP0

9

Operation

WARNING
♦ Motor parameters must be accurately configured for the motor overload

protection to operate correctly.

♦ MICROMASTERS operate at high voltages.

♦ When operating electrical devices, it is impossible to avoid applying

hazardous voltages to certain parts of the equipment.

♦ Emergency Stop facilities according to EN 60204 IEC 204 (VDE 0113) must

remain operative in all operating modes of the control equipment. Any
disengagement of the Emergency Stop facility must not lead to uncontrolled
or undefined restart.

♦ Wherever faults occurring in the control equipment can lead to substantial

material damage or even grievous bodily injury (i.e. potentially dangerous
faults), additional external precautions must be taken or facilities provided to
ensure or enforce safe operation, even when a fault occurs (e.g. independent
limit switches, mechanical interlocks, etc.).

♦ Certain parameter settings may cause the inverter to restart automatically

after an input power failure.

♦ This equipment is capable of providing internal motor overload protection in

accordance with UL508C section 42. Refer to P0610 and P0335, i

2

t is ON by

default. Motor overload protection can also be provided using an external
PTC via a digital input.

♦ This equipment is suitable for use in a circuit capable of delivering not more

than 10,000 symmetrical amperes (rms), for a maximum voltage of 230 V /
460 V when protected by an H, J or K type fuse, a circuit breaker or self-
protected combination motor controller (for more details see Appendix F).

♦ This equipment must not be used as an ‘emergency stop mechanism’ (see

EN 60204, 9.2.5.4).