Watson-Marlow MM420 User Manual

Page 22

Advertising
background image

2 Installation

Issue 10/06

MICROMASTER 420 Operating Instructions

22

6SE6400-5AA00-0BP0

WARNING
♦ Work on the device/system by unqualified personnel or failure to comply with

warnings can result in severe personal injury or serious damage to material.
Only suitably qualified personnel trained in the setup, installation,
commissioning and operation of the product should carry out work on the
device/system.

♦ Only permanently-wired input power connections are allowed. This equipment

must be grounded (IEC 536 Class 1, NEC and other applicable standards).

♦ If a Residual Current-operated protective Device (RCD) is to be used, it must

be an RCD type B. Machines with a three-phase power supply, fitted with
EMC filters, must not be connected to a supply via an ELCB (Earth Leakage
Circuit-Breaker EN50178 Section 5.2.11.1).

♦ The following terminals can carry dangerous voltages even if the inverter is

inoperative:
- the power supply terminals L/L1, N/L2, L3.
- the motor terminals U, V, W, DC+, DC-

♦ Always

wait

5 minutes

to allow the unit to discharge after switching off before

carrying out any installation work.

♦ This equipment must not be used as an ‘emergency stop mechanism’ (see

EN 60204, 9.2.5.4)

♦ The minimum size of the earth bonding conductor must be equal to or greater

than the cross-section of the power supply cables.

CAUTION
The connection of power, motor and control cables to the inverter must be carried
out as shown in Fig. 2-8 on page 33, to prevent inductive and capacitive
interference from affecting the correct functioning of the inverter.