Watson-Marlow MM420 User Manual

Page 24

Advertising
background image

2 Installation

Issue 10/06

MICROMASTER 420 Operating Instructions

24

6SE6400-5AA00-0BP0

Humidity

Relative air humidity

≤ 95% Non-condensing

Altitude

If the inverter is to be installed at an altitude > 1000 m or > 2000 m above sea
level, derating will be required:

80

100

0

1000

2000

3000

4000

Permissible output current

%

Installation altitude in m above sea level

Permissible input voltage

80

100

0

1000

2000

3000

4000

%

Installation altitude in m above sea level

77

Fig. 2-3

Installation altitude

Shock and Vibration

Do not drop the inverter or expose to sudden shock. Do not install the inverter in an
area where it is likely to be exposed to constant vibration.
Mechanical strength to EN 60721-3-3

Deflection:

0.075 mm (10 ... 58 Hz)

Acceleration:

9.8 m/s

2

(> 58 ... 200 Hz)

Electromagnetic Radiation

Do not install the inverter near sources of electromagnetic radiation.

Atmospheric Pollution

Do not install the inverter in an environment, which contains atmospheric pollutants
such as dust, corrosive gases, etc.

Water

Take care to site the inverter away from potential water hazards, e.g. do not install
the inverter beneath pipes that are subject to condensation. Avoid installing the
inverter where excessive humidity and condensation may occur.

Installation and cooling

CAUTION
The inverters MUST NOT be mounted horizontally.

The inverters can be mounted without any clearance at either side.

Allow 100 mm clearance above and below the inverter. Make sure that the cooling
vents in the inverter are positioned correctly to allow free movement of air.

Advertising