Hitachi NJI-350B User Manual

Page 124

Advertising
background image

Chapter 5 Instruction Specifications

5-74

Item number

Application instructions-5

Name

Shift left

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average Maximum

SHL (d, n)

DER

ERR

SD

V

C

Upper case: W

z

z

z

z

38

Lower case: DW

Instruction format

Number of steps

Condition

Steps

SHL (d, n)

3

46

Bit

Word

Double word

Usable I/O

X

Y

R,

M

TD, SS,

CU, CT

WX WY

WR,

WM TC DX DY

DR,

DM

C

o

nstant

Other

d

I/O to be shifted

{

{

{

{

{

n

Number of bits to be
shifted

{

{

{

{

{

The constant is set in
decimal.

Function

• Shifts the contents of d to the left (toward the upper digits) by n bits.
• Sets n bits of SD (R7F2) contents starting with the least significant bit.
• Sets the content of the nth bit from the most significant bit in C (R7F0).

SD

B

SD SD

SD

SD

SD

SD (R7F2)

C (R7F0)

B

d

n bits

Most significant bit (MSB)

Least significant bit (LSB)

Before execution

After execution

n bits

If d is a word:

Designates the shift amount, depending on the contents (0 to 15) of the lower 4 bits (b3 to b0) of n
(WX, WY, WR, WM, TC). (Upper bits are ignored and considered as “0.”)
The n (constant) can be set to 0 to 15 (decimal).

If d is a double word:

Designates the shift amount, depending on the contents (0 to 31) of the lower 5 bits (b4 to b0) of n
(WX, WY, WR, WM, TC). (Upper bits are ignored and considered as “0.”)
The n (constant) can be set to 0 to 31 (decimal).

Notes

• If n is equal to “0,” the shifting is not performed. The previous state is retained in C.

Program example

X00000

LD

X00000

OUT

R7F2

LD

X00001

AND

DIF1

[

SHL

(DR0000,1)

]

LD

R7F0

OUT

Y00100

X00001

DIF1

SHL

(DR0000 ,1 )

R7F2

R7F0

Y00100

Program description

• The R7F2 value is determined by the on/off of X00000.
• The content of DR0000 is shifted to the left by one bit when X00001 rises.

At this time, the value of R7F2 is set in b0 and the value of b31 (b15 of WR1) in R7F0.

• The Y00100 turns on/off depending on the b31 value of DR0000 (b15 of WR1) prior to the shift.

S