background image

Chapter 5 Instruction specifications

5-115

Item number

Transfer command-1

Name

General purpose port communication command

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average

Maximum

TRNS 0 (d, s, t)

DER

ERR

SD

V

C

z

z

z

z

Command format

Number of steps

Condition

Steps

TRNS 0 (d, s, t)

-

5

80

2,078

Bit

Word

Double word

Usable I/O

X

Y

R,
L,
M

TD, SS,
CU, CT

WX WY

WR,
WM

TC DX DY

DR,
DM

Others

d

Dummy

{

s

Parameter area

{

s to s+14

t

Communication control

{

t to t+11

Function

(1) This is a command to send data via general purpose port. It is also possible to receive data after data sending.

(2) Parameter "d" is dummy. Assign WY10. (Actual data in Y100 to Y115 is not influenced.)

(3) Parameter "s" is starting address of parameter table for communication setting.

(4) Parameter "t" is starting address of bit table for communication control.

(5) "s" parameter

[0] Return code

s

s+1

s+4

s+6

s+7

s+9

s+A

s+B

s+C

s+D

s+E

[1] System area
(Do not use this area.)

[2] Timeout

[3] Address of sending area

[4] Reserve area for data sending (word)

[5] Address of receiving area

[6] Reserve area for data receiving (word)

[7] Receiving data length (byte)

[8] Start code

[9] End code

[10] Communication speed

[11] Communication format

: Access forbidden

: User setting area

s+3

[0]

Return code :

Result of TRNS 0 command is set in
lower 8 bits.
Completed

0

Error

≠ 0

[1]

System area :

This area is used by system (CPU) while
TRNS 0 operation. It is not allowed for
users to use this area.

[2]

Timeout :

Timeout setting from command executed
to completed.
=0 : Timeout disabled
≠0 : Timeout enabled [×10ms]
Max. HFFFF

TR

N

S

0

(

d, s, t)

!

If this area is written, CPU might stop operation due to

system error.

C

ons

ta

nt

Advertising